Air Cooled Water Chiller
Rated Cooling Capacity
×1000 kcal/h 81.5
KW 94.8
Input Power (KW) 31.2
Comp. Input Power×Qty. (KW) 12.5×2
Chilled Water Pump Power (KW) 2.2
Comp. Current (A) 49.8
Power Supply 3φ-380V-50HZ
Safety Protection
Phase reversion protection, Phase lack
protection, Overload current protection,
Discharge air temp. protection, Low & High
pressure protection, Low temp. protection,
Water flow protection.
Number of Refrigeration Circuit 2
Capacity Control (%) 0, 50, 100
Refrigerant R22
Condenser Ripple Aluminum Fins around Cooper Pipe
Power lnput of Fan (KW) 4.0
Evaporator Pipe Coil Type:Shell and Tube Type
Water Side Max Pressure (MPa) 1
Dia.of Pipe to Evaporator (inch) 2-1/2"
Chilled Water Flow (L/m) 272.2
Evaporator Water Pressure drop (kPa) 32
Running Noise dB(A) 75
Tank Volume (L) 420
Total weight (Kg) 980
Dimension L×W×H 2200×1180×2200
Welcome to contact our service team for air cooled chiller units if u project needed. We have more than 20 years HVAC experience on air cooled chiller. thanks.